180 HX7+ ASD Installation and Operation Manual
Hz Per User-Defined Unit
Program Utility Parameters Display Units
This parameter allows the user to input a quantity to be displayed on the keypad
that is proportional to the output frequency of the drive.
This feature is useful when the output of a process is moved along at a rate that
is proportional to the output frequency of the drive.
Direct Access Number — F702
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 200.0
Units — Hz/UDU
Frequency Display Resolution
Program Utility Parameters Display Units
The parameter sets the number of decimal places to be displayed during non-
Accel/Decel functions.
Settings:
0 — 1
1 — 0.1
2 — 0.01
Direct Access Number — F703
Parameter Type — Numerical
Factory Default 0.1
Changeable During Run — Ye s
Minimum — 1
Maximum — 0.01
Accel/Decel Special Display Resolution
Program Special Control Accel/Decel Special
This parameter sets the number of decimal places to be displayed for Accel/
Decel functions.
Direct Access Number — F704
Parameter Type — Numerical
Factory Default 0.1
Changeable During Run — Ye s
Minimum — 1
Maximum — 0.01
Prohibit Initializing User Parameters During Typeform
Initialization
Program Special Control Special Parameters
This parameter Enables/Disables the ability to initialize user parameters during
a Type Form initialization.
Settings:
0 — Allowed
1 — Prohibited
Direct Access Number — F709
Parameter Type — Selection List
Factory Default Allowed
Changeable During Run — Ye s
V/f Group
No path available (Direct Access Only)
While operating using the
CN8 Option (LED Keypad)
1 of 4 V/f groups
may be selected and run. Each V/f group is comprised of 4 user-defined
variables: Base Frequency, Base Frequency Voltage, Manual Torque Boost,
and Electronic Thermal Protection.
Settings:
1 — Group 1
2 — Group 2
3 — Group 3
4 — Group 4
Note: Press ESC from the
Frequency Command
screen to access this
parameter.
Direct Access Number — F720
Parameter Type — Selection List
Factory Default 1
Changeable During Run — Ye s
F702 F720