EasyManua.ls Logo

Toshiba HX7+ ASD - Page 190

Toshiba HX7+ ASD
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HX7+ ASD Installation and Operation Manual 181
Stop Pattern
No path available (Direct Access Only)
While operating using the
CN8 Option (LED Keypad)
the Stop Pattern
parameter determines the method used to stop the motor when the stop
command is issued via a Stop command from the
CN8 Option
.
The Decel Stop setting enables the Dynamic Braking system that is setup at
F304 or the DC Injection Braking system that is setup at F250, F251, and
F252.
The Coast Stop setting allows the motor to stop at the rate allowed by the
inertia of the load.
Settings:
0 — Decel Stop
1 — Coast Stop
Note: The Stop Pattern setting has no effect on the Emergency Off
settings of
F603. Press ESC from the
Frequency Command
screen to access this parameter.
Direct Access Number — F721
Parameter Type — Selection List
Factory Default Decel Stop
Changeable During Run — Ye s
Torque Limit Group
No path available (Direct Access Only)
While operating using the
CN8 Option (LED Keypad)
this parameter is
used to select 1 of 4 preset positive torque limits to apply to the active motor.
The settings of profiles 1 – 4 may be setup at F441, F444, F446, and F448,
respectively.
Settings:
1 — Group 1
2 — Group 2
3 — Group 3
4 — Group 4
Note: Press ESC from the
Frequency Command
screen to access this
parameter.
Direct Access Number — F723
Parameter Type — Selection List
Factory Default 1
Changeable During Run — Ye s
Feedback in Panel Mode
No path available (Direct Access Only)
While operating using the
CN8 Option (LED Keypad)
this parameter
Enables/Disables PID feedback control.
Settings:
0 — Enabled
1 — Disabled
Note: Press ESC from the
Frequency Command
screen to access this
parameter.
Direct Access Number — F724
Parameter Type — Selection List
Factory Default Enabled
Changeable During Run — Ye s
CN8 Option (LED Keypad) Override Multiplication Gain
Program Feedback Parameters Override Control
If operating using the
CN8 Option (LED Keypad)
this parameter provides a
value to be used in the event that Setting is selected for the Frequency
Override Multiplying Input (F661).
Direct Access Number — F729
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — -100.00
Maximum — 100.00
F721 F729

Table of Contents

Other manuals for Toshiba HX7+ ASD

Related product manuals