86 HX7+ ASD Installation and Operation Manual
S5 Input Terminal Assignment
Program Terminal Selection Input Terminals
This parameter selects the functionality of the S5 input terminal.
Note: The S5 input terminal may be used without the ASD-Multicom
option board.
Without the ASD-Multicom option board the S5 terminal
assignment information will be stored in volatile memory. The
terminal assignment information will be lost if the system is
powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S5 terminal to 1 of the 68 possible
functions that are listed in
Table 14 on pg. 189.
Direct Access Number — F119
Parameter Type — Selection List
Factory Default Unassigned
Changeable During Run — No
S6 Input Terminal Assignment
Program Terminal Selection Input Terminals
This parameter selects the functionality of the S6 input terminal.
Note: The S6 input terminal may be used without the ASD-Multicom
option board.
Without the ASD-Multicom option board the S6 terminal
assignment information will be stored in volatile memory. The
terminal assignment information will be lost if the system is
powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S6 terminal to 1 of the 68 possible
functions that are listed in
Table 14 on pg. 189.
Direct Access Number — F120
Parameter Type — Selection List
Factory Default Unassigned
Changeable During Run — No
S7 Input Terminal Assignment
Program Terminal Selection Input Terminals
This parameter selects the functionality of the S7 input terminal.
Note: The S7 input terminal may be used without the ASD-Multicom
option board.
Without the ASD-Multicom option board the S7 terminal
assignment information will be stored in volatile memory. The
terminal assignment information will be lost if the system is
powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S7 terminal to 1 of the 68 possible
functions that are listed in
Table 14 on pg. 189.
Direct Access Number — F121
Parameter Type — Selection List
Factory Default Unassigned
Changeable During Run — No