HX7+ ASD Installation and Operation Manual 89
FL Output Terminal Assignment
Program Terminal Selection Output Terminal
This parameter sets the functionality of the FL output terminals to 1 of the 62 
possible functions that are listed in 
Table 16 on pg. 194.
The on and off delay times of the FL terminals may be adjusted to provide 
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or 
Normally Closed.
Direct Access Number —  F132
Parameter Type — Selection List
Factory Default — Fault (All)
Changeable During Run — No
Output #4 Terminal Assignment
Program Terminal Selection Output Terminal
This parameter sets the functionality of the OUT4 terminals to 1 of the 62 
possible functions that are listed in 
Table 16 on pg. 194.
The on and off delay times of the OUT4 terminals may be adjusted to provide 
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or 
Normally Closed.
Direct Access Number —  F133
Parameter Type — Selection List
Factory Default — LL
Changeable During Run — No
OUT5 Terminal Assignment
Program Terminal Selection Output Terminal
This parameter sets the functionality of the OUT5 terminals to 1 of the 62 
possible functions that are listed in 
Table 16 on pg. 194.
The on and off delay times of the OUT5 terminals may be adjusted to provide 
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or 
Normally Closed.
Direct Access Number —  F134
Parameter Type — Selection List
Factory Default — UL
Changeable During Run — No
OUT6 Terminal Assignment
Program Terminal Selection Output Terminal
This parameter sets the functionality of the OUT6 terminals to 1 of the 62 
possible functions that are listed in 
Table 16 on pg. 194.
The on and off delay times of the OUT6 terminals may be adjusted to provide 
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or 
Normally Closed.
Direct Access Number —  F135
Parameter Type — Selection List
Factory Default — RCH (Specified 
Speed)
Changeable During Run — No
F132 F135