7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor thermometer)
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 
B05J2KVG-E 
1.2 to 1.3  
14 to 16
43 to 44
High
High
31
B07J2KVG-E 
1.2 to 1.3 
13 to 14 
46 to 47
High High
42
B10J2KVG-E 
1.1 to 1.2  12 to 13  48 to 49
High High
61
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 
2.2 to 2.3 36 to 37 
1 to 2 
High High
46
2.3 to 2.4  39 to 40  
0 to 1 High High
59
2.3 to 2.4 38 to 40 
0 to 1 High High
78
condition(°C)
Tempeature Heat exchanger
pipe temp.
B05J2KVG-E 
B07J2KVG-E 
B10J2KVG-E 
B13J2KVG-E 
1.0 to 1.1    9 to 11  48 to 49
High High
75
B16J2KVG-E 
1.0 to 1.1    9 to 11  50 to 51
High High
75
2.4 to 2.5   40 to 42  1 to 2
High High
68
2.7 to 2.8   44 to 45  0 to 1
High High
81
B13J2KVG-E 
B16J2KVG-E 
18J2KVG-E
0.8 to 1.0   8 to 9  46 to 47
High High
85.8
2.9 to 3.0   45 to 48  2 to 3
High
High
89.4 
18J2KVG-E
Connecting
piping 
(m)
5.0
7.5
Connecting
piping 
(m)
5.0
7.5