E6581528
C-5
3
4) Setting the frequency using input voltage (0~10Vdc)
[Parameter setting]
5) Setting the frequency using input voltage (0~±10Vdc)
The direction can be changed by switching between positive and negative signals.
[Parameter setting]
Set the “basic parameter frequency setting mode selection 1” parameter

to
.
Note: Set reference frequency priority selection  to (/ terminal switching, default setting).
Changing the settings of two speed command parameters at a time, refer to Section 6.6.
Frequency
0
0Vdc
10Vdc
60Hz
Set the “extended parameter analog input VI/II voltage/current switching”
parameter  to .
In addition, set thebasic parameter frequency setting mode selection 1” parameter
 to
(
default settin
g
).
+
-
RX
CC
A
-10Vdc
+10Vdc
Forward run
Reverse run
60Hz
60Hz
+
-
V
I/II
CC
A
Voltage signal
Voltage signal (0~10V) for setting the operation frequency
Refer to Section 7.3 for details of adjustment.
:Voltage signal 0-10Vdc
Voltage signal
Voltage signal (0~±10V) for setting the operation frequency
Refer to Section 7.3 for details of adjustment.
:Voltage signal 0-±10Vdc