E6581386
E-33
5
[Parameter setting]
Title Function Adjustment range Default setting

Regenerative power ride-through
control selection
:Disabled
:Power ride-through
:Deceleration stop during power failure:

Non-stop control time/Deceleration
time during power failure
~ sec. 

Under voltage detection level
~ %, : Automatic mode 

Regenerative power ride-through control level
~ % 
Note 1: The power ride-through control time when = depends on the setting of , and the
deceleration time when = depends on the setting of .
Note 2: Even if these functions are used, a motor may coast according to load conditions.
In this case, use the auto-restart function along with this parameter function.
Note 3: Although the setting of  can be written when  is set to (non-stop control), it cannot be
written when  is set to (momentary power failure slowdown stop).
Note 4: For the parameter , 100% corresponds to 200V (200V class) or 400V (400V class).
An example of setting when =
[When power is interrupted]
Motor speed
About 100ms
10s
Input voltage
Coasting stop
*1:
Note: If power is interrupted during deceleration stop, powe
r
ride-through control will not be performed.
Internal DC
voltage level


Regenerative power
ride-through control selection
[If momentary power failure occurs]
Motor speed
In
p
ut volta
g
e
*1
:
Note: If power is interrupted during deceleration stop, powe
r
ride-through control will not be performed.
Internal DC
voltage level


Non-stop control
Normal acceleration
The time for which the operation of the motor
can be continued depends on the machine
inertia and load conditions. Before using this
function, therefore, perform verification tests.
Use with the retry function allows the motor to
be restarted automatically without being
brought to an abnormal stop.
*1
*1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals