EasyManua.ls Logo

Toshiba TOSVERT VF-PS1 - Measures to Satisfy the EMC Directive

Toshiba TOSVERT VF-PS1
317 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6581386
I-2
9
9.1.2 Measures to satisfy the EMC directive
Concrete measures for EMC directive of CE markings are shown below.
Models with a built-in EMC filter
(1) 200V class: VFPS1-2004PL~2075PL
400V class: VFPS1-4007PL~4630KPC
The above mentioned models install EMC noise filter inside. So the conducted and radiated noise can be reduced,
optional EMC noise filters are not needed.
(If a further noise reduction is required, insert an additional filter described in I-4 on the input side of the inverter.)
Table 2 EMC directive compliance
Requirements
Inverter type EMC plate type
PWM carrier
frequency
(kHz)
Length of
motor
connecting
cable
(m)
Conducted noise
IEC61800-3 category C2
(EN55011 classA Group1)
Conducted noise
IEC61800-3 category C3
(EN55011 classA Group2)
4 10 VFPS1-2004PL~
VFPS1-2015PL
EMP101Z
16 5
4 10
VFPS1-2022PL
16 5
Built-in filter -
4 10
VFPS1-2037PL
EMP102Z
16 5
4 10 VFPS1-2055PL,
VFPS1-2075PL
EMP103Z
16 5
- Built-in filter
4 10 VFPS1-4007PL~
VFPS1-4022PL
EMP101Z
16 5
4 10
VFPS1-4037PL EMP102Z
16 5
Built-in filter -
4 10 VFPS1-4055PL~
VFPS1-4110PL
EMP103Z
16 5
4 10
VFPS1-4150PL
16 5
2.5 25
VFPS1-4185PL
EMP104Z
16 25
2.5 50
VFPS1-4220PL EMP105Z
16 25
2.5 50 VFPS1-4300PL,
VFPS1-4370PL
EMP106Z
4 25
2.5 50 VFPS1-4450PL~
VFPS1-4750PL
EMP108Z
16 25
VFPS1-4900PC,
VFPS1-4110KPC
- 2.5 50
VFPS1-4132KPC - 2.5 50
VFPS1-4160KPC - 2.5 50
VFPS1-4220KPC - 2.5 50
VFPS1-4250KPC~
VFPS1-4315PL
- 2.5 50
VFPS1-4400KPC,
VFPS1-4500KPC
- 2.5 50
VFPS1-4630KPC - 2.5 50
- Built-in filter
( ): An optional regenerative braking unit PB7 is used.