EasyManuals Logo
Home>Toshiba>Power Supply>TOSVERT VF-PS1

Toshiba TOSVERT VF-PS1 User Manual

Toshiba TOSVERT VF-PS1
317 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #176 background imageLoading...
Page #176 background image
E6581386
F-60
6
6.28 Low torque detectiosn signal
H : Undertorque detection selection
H : Undertorque detection level during power running
H : Undertorque detection level during regenerative braking
H : Undertorque detection time
H : Undertorque detection hysteresis
Function
If the torque remains below the level specified with
H
or
H
for a period longer than that
specified with
H
, the inverter will be tripped. Then the trip message “
WV
” appears.
H=: Alarm signal output (No tripping)
With an output terminal function selection parameter, the inverter can be set so as to issue an
undertorque alarm.
The output terminal function number is 142 or 143 (reverse video).
H=: Trip signal output
If the torque is found to be below the value set with H or Hfor a period longer than that set
with H, the inverter will be tripped. (FL activated under a fault signal)
Title Function Adjustment range Default setting
H Undertorque detection selection
: Alarm mode
: Trip mode

H
Undertorque detection level during
power running
~ % 
H
Undertorque detection level during
regenerative braking
~ % 
H Undertorque detection time ~ sec. 
H Undertorque detection hysteresis ~ % 
<Example of operation>
Output terminal function: 142 (Low torque detection
)
H= (Alarm output)
Ex.) When outputting low torque detection signals through output terminal OUT1
Title Function Adjustment range Setting value
H Output terminal function selection 1(OUT1) ~ 
Note: To put out signals to the terminal OUT2, select the parameter H.
Time [sec]
H
+
H
H
Output torque [%]
Low torque
signal output
H
ON
OFF
less than
H
OFF
When H= (tripping), the inverter will trip if low torque lasts for the period of time set with H.
After tripping, the low torque signal remains ON.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals