6.17 Commercial power/inverter switching
 : Commercial power/inverter switching output selection
 : Commercial power/inverter switching frequency
 : Inverter-side switching waiting time
 : Commercial power-side switching waiting time
 : Commercial power switching frequency holding time
Function
These parameters are used to specify whether to send a switching signal to an external sequencer (such as
an MC) in the event that the inverter trips. The use of an input signal makes it possible to switch between
inverter operation and commercial power operation without stopping the motor.
For details, see Instruction Manual (E6581364) specified in Section 6.36.
[Parameter setting]
Title Function Adjustment range Default setting

Commercial power/inverter
switching output selection
:Disabled
:Automatic switching in the event of a trip
:Commercial power switching frequency setting
:Commercial power switching frequency setting +
automatic switching in the event of a trip [Note1]


Commercial power/inverter
switching frequency
~Hz
Inverter with a
model number
ending with
-WN: 
-WP: 

Inverter-side switching
waiting time
~ sec.
According to
model
Refer to
page K-42.

Commercial power-side
switching waiting time
~ sec. 

Commercial power switching
frequency holding time
~ sec. 
Note: For trips whose causes are displayed with , ,  or , switching is not done automatically.
[Timing chart (example)]
Set frequency
Commercial power/inverter switching frequency

MC output for inverter operation
Commercial power/inverter switching output 1
(P24-OUT1)
MC output for commercial power operation
Commercial power/inverter switching output 2
(P24-OUT2)
Commercial
p
ower switchin
g
si
g
nal
(
S3-CC
)
ON
Commercial power-side switching
waiting time 
Inverter-side switching waiting
time 
Detection time
Commercial power switching frequency
holding time 
ON
ON
ON
Commercial power switching signal S3-CC ON : Commercial power operation
Commercial power switching signal S3-CC OFF : Inverter operation
Note: If ST-CC is opened, switching cannot be operated normally.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals