E6581386
J-7
10
Selection table of separate-type options (2/2)
Voltage
class
Appli
-cable
motor
[kW]
Inverter
model
Input AC
reactor
(ACL)
DC reactor
(DCL)
(*6)
EMC Diredctive
compliant noise
reduction filter
Braking resistor
(*1)
Motor end
surge voltage
suppression
filter
(*4)
Control
power
supply
backup
0.4 VFPS1-2004PL
DCL2-2004
0.75 VFPS1-2007PL
PFL-2005S
DCL2-2007
PBR-2007
1.5 VFPS1-2015PL
DCL2-2015
2.2 VFPS1-2022PL
PFL-2011S
DCL2-2022
PBR-2002
3.7 VFPS1-2037PL PFL-2018S
DCL2-2037
PBR-2037
5.5 VFPS1-2055PL PFL-2025S
DCL2-2055
PBR3-2055
7.5 VFPS1-2075PL
DCL2-2075
Built in
PBR3-2075
11 VFPS1-2110PM
PFL-2050S
PBR3-2110
15 VFPS1-2150PM
EMF3-4074E
18.5 VFPS1-2185PM
PBR3-2150
22 VFPS1-2220PM
PFL-2100S
EMF3-4090F
30 VFPS1-2300PM
PBR3-2220
37 VFPS1-2370PM
PFL-2150S
45 VFPS1-2450PM PFL-2200S
Built in
EMF3-4180H
55 VFPS1-2550P PFL-2300S
PBR-222W002
75 VFPS1-2750P PFL-2400S
EMF3-4300I
200V
class
90 VFPS1-2900P
PFL-2600S
Attached as
standard
EMF3-4600J
DGP600W-B1
[DGP600W-C1]
0.75 VFPS1-4007PL
DCL2-4007
1.5 VFPS1-4015PL DCL2-4015
MSF-4015Z
2.2 VFPS1-4022PL
DCL2-4022
PBR-2007
3.7 VFPS1-4037PL
PFL-4012S
DCL2-4037 PBR-4037
MSF-4037Z
5.5 VFPS1-4055PL
DCL2-4055
PBR3-4055
7.5 VFPS1-4075PL DCL2-4075 PBR3-4075
MSF-4075Z
11 VFPS1-4110PL
PFL-4025S
DCL2-4110 PBR3-4110
15 VFPS1-4150PL
DCL2-4150
MSF-4150Z
18.5 VFPS1-4185PL
PBR3-4150
22 VFPS1-4220PL
PFL-4050S
MSF-4220Z
30 VFPS1-4300PL
PBR3-4220
37 VFPS1-4370PL
MSF-4370Z
45 VFPS1-4450PL
PFL-4100S
55 VFPS1-4550PL
MSF-4550Z
75 VFPS1-4750PL
PFL-4150S
Built in
PBR-417W008
MSF-4750Z
90 VFPS1-4900PC
110
VFPS1-4110KPC
PFL-4300S
132
VFPS1-4132KPC
160
VFPS1-4160KPC
PFL-4400S
DGP600W-B2
[DGP600W-C2]
SWF-4160K
(*7)
220
VFPS1-4220KPC
PFL-4600S
DGP600W-B3
[DGP600W-C3]
SWF-4220K
(*7)
250
VFPS1-4250KPC
280
VFPS1-4280KPC
315
VFPS1-4315KPC
PB7-4200K(*2)
DGP600W-B4
[DGP600W-C4]
SWF-4355K
(*7)
400
VFPS1-4400KPC
PFL-4800S
PB7-4400K(*2)
DGP600W-B3
×2(parallel)
[DGP600W-C3
×2(parallel)]
500
VFPS1-4500KPC
PFL-4450S
×2(parallel)
400V
class
630
VFPS1-4630KPC
PFL-4613S
×2(parallel)
Attached as
standard
Built in
PB7-4400K(*2)
DGP600W-B4
×2(parallel)
[DGP600W-C4
×2(parallel)]
SWF-4630K
(*7)
CPS002Z
(*1): Model in square brackets is fitted with top cover.
(*2): To use a 400V/250kW inverter or larger in combination with an external braking resistor (DGP600 series), a braking unit (PB7) with a built-in braking
resistor drive circuit is also needed.
(*3):
The options are selected based on the premise that 600V HIV insulated wires (continuous allowable temperature: 75°C) are used.
(*4): Each MSF-****Z model is composed of a reactor, a resistor and a capacitor, and as a guide, use a cable 300m or less in length to connect the
inverter to the motor.
Each SWF-****K model is an output-dedicated surge suppression reactor, and as a guide, use a cable 100m or less in length.
(*5): These reactors are usable for each of 200V class and 400V class.
(*6): Be sure to connect DC reactor to 200V-55kW and above models and 400V-90kW and above models. (Not necessary for DC power input.)
When a 200V-55kW and above models or 400V-90 to 280kW models is replaced with new one, the reactor (model: DCL-****) used with the current
inverter can be used as-is with the new inverter. In such cases, therefore, you do not need to purchase any reactors in this table.
(*7): In case of using the SWF filter, set the parameter  to or and set the carrier frequency to 4kHz and above.