K-23
E6581386
11
[26] Operation panel parameters [2/3] Sensorless vector/PG feedback control (●:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Constant
Reference
0740 Trace selection
0:Deselect
1:At tripping
2:At triggering
1/1 1 Enabled ●/● ● ● 6. 32
0741 Trace cycle
0:4ms
1:20ms
2:100ms
3:1s
4:10s
1/1 2 Enabled ●/● ● ● 6. 32
0742 Trace data 1 0~49 1/1 0 Enabled ●/● ● ● 6. 32
0743 Trace data 2 0~49 1/1 1 Enabled ●/● ● ● 6. 32
0744 Trace data 3 0~49 1/1 2 Enabled ●/● ● ● 6. 32
0745 Trace data 4 0~49 1/1 3 Enabled ●/● ● ● 6. 32
0748 Integrating wattmeter retention selection
0:0:Disabled
1:1:Enabled
1/1 0 Enabled ●/● ● ● 6. 33
0749 Integrating wattmeter display unit selection
0:1=1kWh
1:1=10kWh
2:1=100kWh
3:1=1000kWh
4:1=10000kWh
1/1 *2 Enabled ●/● ● ● 6. 33
0750 EASY key function selection
0:Quick mode/standard setting mode switching
function
1:Shortcut key:Pressing for 2 sec. to record the
parameter, pressing normally to jump
to recorded parameter (first jump to
the 1st history)
2:Local/remote key:Local by ON
3:Monitor peak minimum hold trigger
1/1 0 Disabled ●/● ● ● 5. 22
0751 Quick registration parameter 1 0~999 *1 1/1
40
(AU4)
Enabled ●/● ● ● 5. 22
0752 Quick registration parameter 2 0~999 *1 1/1
15
(pt)
Enabled ●/● ● ● 5. 22
0753 Quick registration parameter 3 0~999 *1 1/1
11
(FH)
Enabled ●/● ● ● 5. 22
0754 Quick registration parameter 4 0~999 *1 1/1
9
(ACC)
Enabled ●/● ● ● 5. 22
*1: The communication number of the parameter is used for this setting.
*2: Default values vary depending on the capacity. See the table of K-42.