EasyManuals Logo
Home>Toshiba>Power Supply>TOSVERT VF-PS1

Toshiba TOSVERT VF-PS1 User Manual

Toshiba TOSVERT VF-PS1
317 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #55 background imageLoading...
Page #55 background image
E6581386
B-13
2
Te r m i n a l
symbol
Input/
output
Function (Sink Source logic)
Electrical
specifications
Inverter internal circuits
CCA
*1
Common
to input/
output
Analog input/output signal equipotential (0V)
terminal for the control circuit.
- -
+SU Input
DC power input terminal for operating the
control circuit. Connect a control power backup
device (optional) between +SU and CC.
Voltage:24Vdc±10%
Use a power supply
with a current rating
of 1.05A or more.
(In case of not install
options, current rating
is 300mA )
FLA
FLB
FLC
Output
Relay contact output. Contact rating
Used to detect the activation of the inverter's
protective function. Contact across FLA-FLC is
closed and FLB-FLC is opened during
protection function operation.
250Vac-2A
30Vdc-1A
:at resistance load
250Vac-1A
:cos=0.4
*1: Although the CC terminal and the CCA terminal are not insulated, they should be used separately, one for the logic circuit and
the other for the analog circuit
*2: The PWR terminal is not the same as the ST (standby signal input) terminal provided for conventional models. To use the ST
function, assign it to a multifunction terminal (F, R, RES or S1 to S4) that is not currently in use.
Example: When assigning the ST function to the S3 terminal,
Set  to (to cancel its factory default setting: = ST always active), and
Set  to (to assign the ST function to the S3 terminal).
These settings put the motor into a standby state if S3 and CC are short-circuited, or coast and stop the motor if
the circuit between S3 and CC is opened.
For PWR connection conforming to safety standards, refer to Section 9.3.
SW SW settings
Default setting
(Settings marked
with )
Function
(-WN)
Setting for using the inverter’s internal power supply in sink logic
mode
Setting for using the inverter’s external power supply in sink logic
mode
SW1
(-WP)
Setting for operating the inverter in source logic mode
Setting for using the analog output terminal FM to output current
of 0-1mA
SW2
Setting for using the analog output terminal FM to output current
of 0-10V or 0-20mA (4-20mA)
0-10V (=) or 0-20mA (=) can be selected by
changing parameter settings.
Setting for using the input terminal RR/S4 as an analog input
terminal (0-10Vdc)
SW3
Setting for using the input terminal RR/S4 as a contact input
terminal
Setting for using the output terminal OUT1 as a logic output
terminal
When turning the switch to this position, always set the
parameter  to (logic output).
SW4
Setting for using the output terminal OUT1 as a pulse output
terminal
When turning the switch to this position, always set the
parameter  to (pulse output).
SOURCE SINK
PLCINT/PLC INT
SOURCE SINK
PLCINT/PLC INT
SOURCE SINK
PLCINT/PLC INT
0-10V
0-20mA
0-1mA
FM
0-10V
0-20mA
0-1mA
FM
S4
RR/S4
RR
S4
RR/S4
RR
PULS LO
OUT1
PULS Lo
OUT1
P24
0.5
+SU
CC
P24
FL
FLA
FLB
FLC

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals