EasyManua.ls Logo

Toshiba TOSVERT VF-PS1 - Page 62

Toshiba TOSVERT VF-PS1
317 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6581386
C-4
3
Frequency setting
1) Setting the frequency using potentiometer
[Parameter setting]
Set the “basic parameter frequency setting mode selection 1” parameter

to
.
(There is no need to set this parameter before the first use after purchase.)
2) Setting the frequency using input voltage (0~10V)
[Parameter setting]
Set the “basic parameter frequency setting mode selection 1” parameter

to
.
(There is no need to set this parameter before the first use after purchase.)
3) Setting the frequency using current input (4(0)~20mA)
[Parameter setting]
+
-
RR
/
S4
CC
A
Frequency
0
0Vdc
10Vdc
Voltage signal
Voltage signal (0~10V) for setting the operation frequency
Refer to Section 7.3 for details of adjustment.
60Hz
:Voltage signal 0-10Vdc
V
I/II
CC
A
Frequency
0
4mAdc
20mAdc
Current signal
Current signal (4(0)~20mA) for setting the operation frequency
Refer to Section 7.3 for details of adjustment.
60Hz
:Current signal 4(0)-20mAdc
+
-
Set the basic parameter frequency setting mode selection 1” parameter  to .
In addition, set theextended parameter analog input VI/II voltage/current
switching” parameter
 to .
To bring the operation frequency to 0Hz at an input current of 4mA, set the “VI/II input
point setting 1” parameter
 to .
PP
CC
A
:Frequency settings
With potentiometer
MIN
MAX
Frequency
60Hz
0
MIN MAX
RR
/
S4
Potentiometer
The operation frequency by potentiometer (1k~10k- 1/4W ) for setting
Refe
r
to Section 7.3 for details of ad
j
ustment.

Table of Contents