CG-SVX17D-EN 63
Installation - Mechanical
Figure 50. Ethylene glycol performance factor - capacity adjustment
0.976
0.978
0.98
0.982
0.984
0.986
0.988
0.99
0.992
0.994
0.996
0 5 10 15 20 25 30 35 40 45
ADJUSTMENT FACTOR
% ETHYLENE GLYCOL BY WEIGHT
60 Hz
50 Hz
Figure 51. Propylene glycol performance factor - capacity adjustment
0.955
0.96
0.965
0.97
0.975
0.98
0.985
0.99
0.995
05
10
15 20 25 30 35 40 45 50
ADJUSTMENT FACTOR
% PROPYLENE GLYCOL BY WEIGHT
60 Hz
50 Hz