RT-SVX24Q-EN
163
Table 57. Standard units with ERW field measured plenum pressure Standard CFM ERW 90-162 Tons
90/100 Ton Standard CFM ERW - Field measured plenum pressure (inches wc)
CFM
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45 50
Econ
Traq
Econ
Traq
Econ
Traq
Econ
Traq
Econ
Traq
Econ
Traq
E/T E/T E/T E/T E/T E/T E/T E/T
16000 1.26 0.84 1.49 0.68 1.02 0.61 0.81 0.57 0.61 0.55 0.6 0.43 0.42 0.4 0.38 0.35 0.32 0.29 0.17
20000 1.95 1.3 2.3 1.05 1.57 0.93 1.24 0.88 0.93 0.85 0.92 0.64 0.63 0.61 0.57 0.52 0.48 0.43 0.25
25000 2 1.62 2.42 1.43 1.9 1.34 1.42 1.3 1.41 0.97 0.95 0.92 0.86 0.79 0.71 0.64 0.35
30000 2.84 2.28 2.02 2.69 1.89 1.99 1.82 1.97 1.35 1.32 1.27 1.19 1.08 0.97 0.87 0.46
33000 2.74 2.42 2.26 2.38 2.18 2.36 1.61 1.58 1.51 1.42 1.29 1.16 1.03 0.53
36000 2.86 2.67 2.81 2.57 2.78 1.89 1.85 1.77 1.66 1.5 1.35 1.2
40000 2.28 2.23 2.14 2 1.81 1.61 1.44
105/118 Ton Standard CFM ERW - Field measured plenum pressure (inches wc)
CFM
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45 50
Econ
Traq
Econ
Traq
Econ
Traq
Econ
Traq
Econ
Traq
Econ
Traq
E/T E/T E/T E/T E/T E/T E/T E/T
19000 1.76 1.17 2.07 0.95 1.42 0.84 1.12 0.79 0.84 0.76 0.83 0.58 0.57 0.55 0.52 0.47 0.43 0.39 0.22
23000 2.55 1.69 1.36 2.05 1.21 1.61 1.13 1.2 1.09 1.19 0.82 0.8 0.77 0.73 0.66 0.6 0.54 0.3
28000 2.47 1.99 3 1.76 2.34 1.64 1.73 1.59 1.72 1.18 1.15 1.11 1.04 0.94 0.85 0.76 0.4
33000 2.72 2.4 2.24 2.36 2.16 2.34 1.59 1.55 1.49 1.39 1.26 1.13 1.01
38000 2.92 2.82 2.05 2.01 1.92 1.8 1.62 1.45 1.29
43000 2.57 2.51 2.41 2.24 2.02 1.8 1.59
45000 2.8 2.73 2.62 2.44 2.19 1.95 1.73
120/128 Ton Standard CFM ERW - Field measured plenum pressure (inches wc)
CFM
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45
Econ
Traq
Econ
Traq
Econ
Traq
Econ
Traq
Econ
Traq
Econ
Traq
E/T E/T E/T E/T E/T E/T E/T
21000 1.48 1.02 1.63 0.84 1.02 0.76 0.83 0.72 0.81 0.7 0.68 0.51 0.5 0.47 0.44 0.38 0.33 0.28
26000 2.23 1.53 2.47 1.26 1.52 1.13 1.24 1.07 1.21 1.04 1.01 0.75 0.73 0.69 0.63 0.55 0.47 0.4
31000 2.13 1.75 2.12 1.57 1.72 1.48 1.67 1.43 1.4 1.02 0.99 0.94 0.85 0.74 0.62 0.52
36000 2.83 2.31 2.81 2.07 2.27 1.95 2.2 1.89 1.84 1.34 1.29 1.22 1.11 0.95 0.79 0.65
41000 2.95 2.63 2.89 2.47 2.8 2.39 2.33 1.68 1.62 1.53 1.38 1.18 0.98
46000 2.96 2.88 2.06 1.99 1.87 1.68 1.43 1.17
UUnniitt SSttaarrttuupp

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak 2 Series and is the answer not in the manual?

Trane IntelliPak 2 Series Specifications

General IconGeneral
BrandTrane
ModelIntelliPak 2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals