EasyManua.ls Logo

Trane mP30 - Page 12

Trane mP30
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTRUCTION MANUAL
UG30 CONTROL
12 (44)
mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN
Dip switch 1-not used
Dip switch 2 set to ON: Relay not energized (contact open) with at least one alarm active, otherwise energized
(contact closed)
Dip switch 3 set to ON
Dip switch 4 set to OFF
. Dip switches type A (alarm relay and maximum production settings)
A1
A2 A3 A4
ON
X
OFF
X
Dip switch 1-not used
Dip switch 2 set to ON: Relay not energized (contact open) with at least one alarm active, otherwise energized
(contact closed)
Dip switch 3 set to OFF
Dip switch 4 set to ON
Dip switches type B (auxiliary functions and automatic draining time)
B1 B2 B3 B4 B5 B6 B7 B8
ON
OFF
Dip switch 1 set to OFF: complete draining after 7 days without production being requested (function
enabled)
Dip switch 2 set to OFF: automatic draining with or without electrode power supply (electrodes not
supplied)
Dip switch 3 set to OFF: the new production setpoint is reached by means of evaporation cycles when
demand is reduced by less than 25%. Draining is achieved by means of evaporation cycles.
Dip switch 4 set to OFF: cylinder exhaustion advance warnings (alarms are displayed when the cylinder
is approaching exhaustion).
Dip switches 5-6 set to OFF: automatic draining time (default setting)
Dip switches 7-8 set to OFF: Evaporation time threshold (default setting)
The “TA RATE” dip switches are left in their default positions since an external TAM is being used
Jumper setting on external TAM
IN MERCURY/MERCURY BIG MODELS, THE JUMPER MUST BE PLACED IN POSITION
100 (END OF SCALE IS QUANTIFIED IN AMPERES 100=10 AMPERES)
50% of nominal steam flow FRAME 1-2
BIG
75% of nominal steam flow FRAME 3-4 & BIG

Related product manuals