52 RT-SVD03G-EN
ReliaTel Test Mode
Table 14. Odyssey Independent Circuit Heat Pump Units 15-20 Ton
Step Mode IDM Econ CPR1 CPR2 HT1 HT2 SOV 1 SOV 2 ODM1 ODM2
1 Fan On On Min Off Off Off Off Off Off Off Off
2* Econ. On Open Off Off Off Off On On Off Off
3 Cool 1 On Min On Off Off Off On On On Off
4 Cool 2 On Min On On Off Off On On On On
5 Heat 1 On Min On Off Off Off Off Off On Off
6 Heat 2 On Min On On Off Off Off Off On On
7* Heat 3 On Min On On On Off Off Off On On
8* Heat 4 On Min On On On On Off Off On On
9**DefrostOnMinOnOnOnOffOnOnOffOff
10 Em. Heat On Min Off Off On On Off Off Off Off
*With Optional Accessory
**Defrost cycle in test mode runs for at least 1 minute, up to 10 minutes, depending on outdoor ambient and outdoor coil temperature.
Steps for optional accessories and modes not present in unit will be skipped.
Table 15. Gas/Electric Units 3-25 Ton
Step Mode IDM Econ CPR1 CPR2 HT1 HT2 Mod Gas* ODM1 ODM2
1 Fan On On Min Off Off Off Off Off Off Off
2* Econ. On Open Off Off Off Off Off Off Off
3 Cool 1 On Min On On(1) Off Off Off On **
4 Cool 2 On Min On On(2) Off Off Off On **
5 Cool 3 On Min On On Off Off Off On **
6* Reheat On Min On On Off Off Off On **
7* Heat 1 On Min Off Off On Off 50% Off Off
8* Heat 2 On Min Off Off On On 100% Off Off
* With Optional Accessory
** "Off" if OAT falls below 60°F, "On" if OAT rises above 65°F. During Reheat, if the unit is configured with 1 compressor, ODM2 is "Off" if the OAT falls
below 70F, "On" if the OAT rises above 75F.
1. CPR2 ON during Cool 1 if configured for 3-Step Cooling; CPR1 OFF.
2. CPR2 OFF during Cool 2 on a 3-Step Cooling unit.
Steps for optional accessories and modes not present in unit will be skipped.
Table 16. Voyager Commercial VAV Service Test with Reheat and Statitrac
Test
Step MODE
IGV/
VFD
(1)
FAN Econ*
EXH
FAN
(2)
*
POWER
EXHAUST
DAMPER*
COMP
1
COMP
2H1*H2*
Mod.
Heat*
Cool
Valve
*
Reheat
Valve*
Reheat
Pump
out*
VHR
Relay
(3) OHMS
1
IGV/
VFD
TEST
OPEN/
100%
OFF
CLOSE
D
OFF MIN OFF OFF OFF OFF 0% 100% 0% OFF ON 2.2k
2
IGV/
VFD
TEST
CLOSED
/0%
OFF
CLOSE
D
OFF MIN OFF OFF OFF OFF 0% 100% 0% OFF ON 3.3k
3
MINIM
UM
VENTIL
ATION
IN CON-
TROL
ON MIN OFF MIN OFF OFF OFF OFF 0% 100% 0% OFF ON 4.7k
4
ECONO
MIZER
IN CON-
TROL
ON 100% ON 100% OFF OFF OFF OFF 0% 100% 0% OFF ON 6.8k