Start-Up and Shutdown
54 RTAF-SVX001A-EN
Stopped to Starting
Figure 45 shows the timing from a stopped mode to
energizing the first compressor.The shortest allowable
time would be under the following conditions:
• No motor restart inhibit time left from subsequent
starts
• Evaporator Water flow occurs quickly with pump on
command
• Need to cool (differential to start) already exists
The above conditions would allow a compressor to start in
about 20 seconds.
Figure 45. Sequence of events: stopped to starting