28 BAS-SVX45F-GB
Wiring Inputs and Outputs
Wiring Inputs and Outputs
Wiring and configuration for UC600 inputs and outputs is described in this section. Refer to Table 2,
p. 9 for a complete list of device connections and descriptions of each type.
Important: If there are problems after powering, refer to the troubleshooting section,
“Commissioning/Troubleshooting in a Powered State,” p. 66.
Input/Output Requirements
All input/output wiring for the Tracer UC600 must meet the following requirements:
All wiring must be in accordance with the National Electrical Code and local codes.
•Do NOT run input/output wires in the same wire bundle with AC-power wires.
Use only 18–22 AWG (1.02 mm to 0.65 mm diameter), stranded, tinned-copper, shielded,
twisted-pair wire.
Binary output wiring must not exceed 300 m.
Binary input and 0–20 mA input wiring must not exceed 300 m.
Analog and 24 VDC output wiring distances are dependent on the specifications of the receiving
unit. Use shielding for analog and 24 VDC outputs.
Thermistor input and 0–10 VDC input or output wiring must not exceed 100 m.
Avoid Equipment Damage!
Remove power to the Tracer UC600 controller before making input or output connections.
Failure to do so may cause damage to the controller, power transformer, or input/output devices
due to inadvertent connections to power circuits.
Table 9. Maximum wire lengths
Maximum Wire Lengths
Type Inputs Outputs
Binary 300 m 300 m
0–20 mA 300 m 300 m
0–10 VDC 100 m 100 m
Thermistor/Resistive 100 m Not Applicable