70 BAS-SVX45F-GB
Commissioning/Troubleshooting in a Powered State
24 Vac Measurement
A
O
6
UI
14
A
O
5
UI
13
A
O
4
UI
12
A
O
3
UI
11
A
O
2
UI
10
A
O
1
UI
9
B
O
4
B
O
3
B
O
2
B
O
1
RELAYS
0
.
5
A MAX
IM
C
1
IM
C
P
1
UI
8
UI
7
UI
6
UI
5
UI
4
UI
3
UI
2
UI
1
IMC
+
24
VDC
LINK
OUT
+
24
VDC
+
24
VDC
OUT
24
VAC
MBUS
OUT
24
VAC
XFMR
24
VAC
SERVICE TOOL
SERVI
C
E
LINK
ACT
IM
C
MBUSLINK
RX
TX
U
C
600
ADDRESS
0
1
2
3
4
5
6
7
8
9
x1
0
1
2
3
4
5
6
7
8
9
x10
0
1
2
3
4
5
6
7
8
9
x100
B
O
4
B
O
3
B
O
2
B
O
1
General Information Checkout Procedure Measurement Expected Value
Checking the voltage that powers
the UC600 is often a necessary step
when commissioning or
troubleshooting. Operational issues
and LED operation may result in a
need to measure the input power.
When troubleshooting, it is faster to
take measurements while the load is
in place. If Step 1 indicates an out-
of-specification voltage, disconnect
the UC600 and measure the AC
voltage across the transformer.
These measurements can direct you
toward the problem source.
Step 1
Measure AC voltage with the
UC600 connected. Perform this
measurement while the unit is
under load.
20.0 Vac V
ac
30.0 Vac
Step 2
Measure AC voltage with the
UC600 unconnected. Perform this
measurement while the unit is not
under load.
20.0 Vac V
ac
30.0 Vac