BAS-SVX45F-GB 33
Wiring Inputs and Outputs
Wiring Variable Resistance Analog Inputs
Variable resistance analog inputs include 10K thermistors, resistance temperature detectors (RTD),
and setpoint thumbwheels on zone sensors. To wire a variable resistance analog input:
1. Connect the shield to a common terminal at the terminal board and tape it back at the input
device.
2. Connect the signal wire to an available input terminal.
3. Use the Tracer TU service tool to configure the analog input that references the corresponding
hardware termination.
Figure 13. Typical wiring, variable resistance
A
O
6
UI
14
A
O
5
UI
13
A
O
4
UI
12
A
O
3
UI
11
A
O
2
UI
10
A
O
1
UI
9
B
O
4
B
O
3
B
O
2
B
O
1
RELAYS
0
.
5
A MAX
IM
C
1
IM
C
P
1
UI
8
UI
7
UI
6
UI
5
UI
4
UI
3
UI
2
UI
1
IMC
+
24
VDC
LINK
OUT
+
24
VDC
+
24
VDC
OUT
24
VAC
MBUS
OUT
24
VAC
XFMR
24
VAC
SERVICE TOOL
SERVI
C
E
LINK
ACT
IM
C
MBUSLINK
RX
TX
U
C
600
ADDRESS
0
1
2
3
4
5
6
7
8
9
x1
0
1
2
3
4
5
6
7
8
9
x10
0
1
2
3
4
5
6
7
8
9
x100
B
O
4
B
O
3
B
O
2
B
O
1
Variable
resistance
Temperature Sensor
Signal
Signal
Common
Common
Tape back shield
Tape back shield
AO/UI connections located on
the bottom tier can also be used.
Wire the same way as shown on
the top tier.