Page #40 background imageLoading...
Page #40 background image
40 BAS-SVX45F-GB
Tracer UC600 Operation
Connection Problems
Problem: Tracer UC600 is not responding, communicating, or is unable to connect with Tracer SC
or the Tracer TU service tool. (For more information about the Tracer TU service tool, see
“Configuring Tracer UC600 with Tracer TU,” p. 41.)
Possible cause: Defective application code in the controller.
Possible solution: Reload the application firmware.
1. Power down the controller (make sure to disconnect the USB cable).
2. Continuously hold down the service button pin while applying power. Press the service button
until the power LED illuminates green. Connect with Tracer TU and reload the application
firmware.
Note: During the above process, the service LED will be green and the communication status LEDs
will be inactive.