ECM Overview and Setup
UNT-SVX07E-EN 99
Table 42. Configuration settings of the motor control board for fan coil and cabinet heater units
Description on
Unit Label
User
Interface
Name
Typical User
Interface
Value Description
Note: These notes are provided for reference only,
and the motor control board label must be
used as the ultimate guide for setting up an
motor control board on specific units.
Mtr 1 High Spd
 
Sets the high-speed rpm for Motor 1.
Do not exceed 2300 rpm.
Mtr 1 Med Spd
 
Sets the medium-speed rpm for Motor 1.
Mtr 1 Low Spd
 
Sets the low-speed rpm for Motor 1.
Do not set under 600 rpm.
EHStg1 Mtr1 Spd

Assigns an rpm to be associated with a call for
1
st
stage electric heat, for Motor 1 (only on units
equipped with electric heat).

,

,

,

settings are
locked out on units with electric heat.
EH Stg 2 Mtr 1 Spd

Assigns an rpm to be associated with a call for
2
nd
stage electric heat, for Motor 1 (only on
electric heat equipped units).
AI High Spd Mtr 1

Sets the maximum rpm for Motor 1 for the
maximum input value of the analog input.
Analog inputs below the

setting will be
rejected.
AI Low Spd Mtr 1

Sets the minimum turn-on rpm for Motor 1,
when the analog input becomes active.
Mtr 2 Hgh Spd

Sets the high-speed rpm for Motor 2.
Blower coils have only one motor.
Mtr 2 Med Spd

Sets the medium-speed rpm for Motor 2.
Mtr 2 Low Spd

Sets the low-speed rpm for Motor 2.
EHStg1 Mtr2 Spd

Assigns an rpm to be associated with a call for
1
st
stage electric heat, for Motor 2 (only on
electric heat equipped units).
If the unit has only one motor, all seven speed
settings for the second motor
(

,

,

,

,

,

,

) should be set to zero.
EH Stg 2 Mtr 2 Spd

Assigns an rpm to be associated with a call for
2
nd
stage electric heat, for Motor 2 (only on
electric heat equipped units).
AI High Spd Mtr 2

Sets the maximum rpm for Motor 2 for the
maximum input value of the analog input.
AI Low Spd Mtr 2

Sets the minimum turn-on rpm for Motor 2,
when the analog input becomes active.
Op Mode Mtr 1
 
Sets the operational mode for Motor 1.
Must be set to

for blower coil units.
Op Mode Mtr 2
 
Sets the operational mode for Motor 2.
Must be set to

for blower coil units.
Mtr 1 Out Format
 
Sets the interface type for Motor 1.
Must be set to

for blower coil units.
Mtr 2 Out Format
 
Sets the interface type for Motor 2
Must be set to

for blower coil units.
Mtr 1/2 PWM Freq.
 
Sets the PWM frequency, for cases when the
PWM outputs are used.
On blower coil units, the

must not be
changed.
Mtr 1 PWM Volt

Sets the PWM voltage, for cases when the PWM
outputs are used.
This setting must NOT be changed, as damage to
the motor may occur!
Mtr 2 PWM Volt

Sets the PWM voltage, for cases when the PWM
outputs are used.
This setting must NOT be changed, as damage to
the motor may occur!
Mt1 Hgh PWM Lt
 
Sets the maximum output percentage that the
controller will request from Motor 1.
This envelope protection value should not be
altered.
Mt1 Low PWM Lt
 
.
Sets the minimum maximum output percentage
that the controller will request from Motor 1.
This envelope protection value should not be
altered.
Mt2 Hgh PWM Lt
 
Sets the maximum output percentage that the
controller will request from Motor 2.
This envelope protection value should not be
altered.
Mt2 Low PWM Lt
 
.
Sets the minimum maximum output percentage
that the controller will request from Motor 2.
This envelope protection value should not be
altered.
Mt1 Ovspd RPM
 
Selects the rpm above which the Motor 1 will be
assumed to be in an overspeed condition and will
need to be shut down.
This envelope protection value should not be
altered.
Mt2 Ovspd RPM
 
Selects the rpm above which the Motor 2 will be
assumed to be in an overspeed condition and will
need to be shut down.
This envelope protection value should not be
altered.
Fan Proving Fct
 
Selects which mode should be assigned to the
Binary output circuit, depending on unit type.
This setting has to be correct for proper unit
operation of electric heat and changeover units.

Table of Contents

Other manuals for Trane UniTrane Fan-Coil

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane UniTrane Fan-Coil and is the answer not in the manual?

Trane UniTrane Fan-Coil Specifications

General IconGeneral
BrandTrane
ModelUniTrane Fan-Coil
CategoryHeater
LanguageEnglish

Related product manuals