“LIVELINK INSTALL” APP / ROOM ADMINISTRATION / SETTINGS: ADVANCED SENSOR SETTINGS Page 63 / 77
Parameter
Default
setting
Variables Explanation
Presence detection
SwitchMode SwitchBoth Fully automatic operation
Semi-automatic operation
Fully/semi-automatic operation
Fully automatic: Switching on and off automatically
Semi-automatic: Switching off automatically,
switching on manually via push-button
shutOffDelay 5 minutes 0-60 minutes Shut-off delay in minutes
switchOffTimeOut
0-3600
seconds
is set in the Use Case Inverse time of presence detection. Time that must pass with-
out movement after a manual intervention in order to return to
automatic operation.
TurnOnValue 100 % is set in the Use Case Is part of the control. If the control is switched on again via a
presence sensor in “light mode”, this start value is used. In
case of a configuration that loads the default scene upon being
switched on, this value is pointless and is not being utilised
Constant light control
SwitchMode SwitchBoth SwitchBoth
OnlySwitchON
OnlySwitchOFF
Switching behaviour in case of sufficient daylight
SwitchBoth: Switching on and off automatically in case
of a sufficient share of daylight
OnlySwitchOn: No daylight-depending switching off,
the illumination remains at
a minimum level
OnlySwitchOFF: Automatic daylight-dependent switching
off, but not switching back on upon drop-
ping below the target value
ShutOFFDelay 300 0-3600 seconds Shut-off delay at the control after exceeding the turn-off
threshold
TurnOffThreshold 25 % 0-100 %
Turn-off threshold, at which the system turns the illumination off
NominalValue 500 lx 0-1024 lx Target value to which the system adjusts
(measured at the sensor)
Dogleg 235 0-254 Breakpoint at which the set offset is regulated to 0
SlowWindow 5 0-20
Range around the nominal value in which no control is exercised
SlowWindowStep 1 0-20 Step width around the nominal value
FastWindow 10 0-40 Other ranges in which control is exercised at reduced speed
FastWindowStep 3 0-20 Step width in other ranges
SpeedDown 2 0-20 Speed of adjusting down
SpeedUp 0 0-20 Speed of adjusting up