INTRODUCTION / BEHAVIOUR OF LIGHT CONTROL / BEHAVIOUR IN DELIVERY CONDITION Page 14 / 77
BEHAVIOUR IN DELIVERY CONDITION
If the control device and the luminaires were already installed, but
the light control was not installed, yet, the lighting can be switched
and dimmed nevertheless (touch/dim function). Operation can be
performed via any push-button connected to the control device:
Short push of button: Turning all luminaires on or off
Long push of button: Dimming all luminaires
The touch/dim function allows for a quick testing of the installation of
all push-buttons and luminaires.
Caution: Initially, the touch/dim function is only available in
delivery condition.
During a configuration process, the function is not
available, but can be re-assigned to select push-buttons.
BEHAVIOUR IN OPERATION
The behaviour of the light control depends on how the system is being
switched on:
Fully automatic presence detection
Starting a scene with semi-automatic presence detection
Starting a scene with light control
Manual switching on of select or all luminaire groups
The decisive factor is, which controls (presence detection, light
control) are contained in the default scene. In the public Use Cases,
the respective most important scene is set as the default scene. In a
lot of cases, this is an automatic scene with fully automatic presence
detection and light control.
Additional information regarding this can be found in the chapter
“What is a Use Case? / Public Use Cases”.
On the following pages, the behaviour of the light control in the differ-
ent situations is shown.
BEHAVIOUR OF LIGHT CONTROL

Other manuals for Trilux LiveLink

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trilux LiveLink and is the answer not in the manual?

Trilux LiveLink Specifications

General IconGeneral
TypeControl Unit
Input Voltage230V AC
Frequency50/60 Hz
Protection RatingIP20
Communication ProtocolsDALI
Mounting OptionsDIN rail