INTRODUCTION / BEHAVIOUR OF LIGHT CONTROL / BEHAVIOUR IN DELIVERY CONDITION
Szene
i
Page 15 / 77
Scene
i
If the default scene contains presence detec-
tion with fully automatic operation, the lighting
starts with the default scene upon entering the
room.
If the scene additionally contains constant light
control, the overall illumination (from daylight
and artificial light) is continuously being ad-
justed to the pre-set target value.
If the default scene contains presence detec-
tion with semi-automatic operation, the scene
is started with a push-button or with a tablet
and/or smart phone.
If the scene additionally contains constant light
control, the overall illumination (from daylight
and artificial light) is continuously being ad-
justed to the pre-set target value.
The illumination ad-
justs itself to the
changed daylight.
In case of a manual intervention, the dim-
ming and switching of luminaire groups, the
constant light control is deactivated for these
luminaire groups. During the stay in the room,
the changed dimming levels of the illumina-
tion are retained.
CHANGE OF THE SCENE
If a change is made to a scene that contains
other operating modes (constant light control
and presence detection), the behaviour does,
of course, change as well (see other pages in
this chapter).
In case of strong ingress of sunlight, the illu-
mination initially dims to a minimum. If the
overall illumination exceeds the target value
by 25 % for more than 5 minutes, the illumi-
nation turns off.
If the daylight be-
comes less, the illumi-
nation switches itself
on again and adjusts
to the target value.
Subsequent to a subsequent holding time,
the illumination turns off after the room has
been left.
The presence detection remains maintained
even after a manual change of the illumi-
nation. Subsequent to a subsequent holding
time, it turns the illumination off after the
room has been left.
• CONSTANT LIGHT CONTROL
PRESENCE DETECTION
(AUTOMATIC OPERATION)
• CONSTANT LIGHT CONTROL
PRESENCE DETECTION
(SEMI-AUTOMATIC OPERATION)
ADVANCED SETTINGS
Through advanced settings in the default
scene, a switching on again of the illumina-
tion upon dropping below the target value can
be prevented.

Other manuals for Trilux LiveLink

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trilux LiveLink and is the answer not in the manual?

Trilux LiveLink Specifications

General IconGeneral
TypeControl Unit
Input Voltage230V AC
Frequency50/60 Hz
Protection RatingIP20
Communication ProtocolsDALI
Mounting OptionsDIN rail