Operating
Process input data
116
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
10 Operating
10.1 Process input data
Word
no.
Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Basic
0x00 - - - - - - - - DXP7 DI6
(SIO)
DXP5 DI4
(SIO)
DXP3 DI2
(SIO)
DXP1 DI0
(SIO)
0x01 - - - - - - - - - DVS6 - DVS4 - DVS2 - DVS0
IO-Link process input data
0x02
…
0x11
IO-Link port 1,
structure depends on the channel parameterization (0…32 byte per channel)
0x12
…
0x21
IO-Link port 2,
structure depends on the channel parameterization (0…32 byte per channel)
0x22
…
0x31
IO-Link port 3,
structure depends on the channel parameterization (0…32 byte per channel)
0x32
…
0x41
IO-Link port 4,
structure depends on the channel parameterization (0…32 byte per channel)
Diagnostics
DXP channels
0x42 - - - - - - - - ERR
DXP 7
- ERR
DXP 5
- ERR
DXP 3
- ERR
DXP 1
-
IO-Link port 1
0x43 GEN-
ERR
OVL V
HIGH
V
LOW
ULVE LLVU O
TMP
PRM
ERR
EVT1 EVT2 PD
INV
HW
ERR
DS
ERR
CFG
ERR
PPE -
0x44 IO-Link port 2, assignment similar to port 1
0x45 IO-Link port 3, assignment similar to port 1
0x46 IO-Link port 4, assignment similar to port 1
IO-Link Events
0x47 Port (1st Event) Qualifier (1st Event)
0x48 Event Code low byte (1st Event) Event Code high byte (1st Event)
…
0x65 Port 16th Event) Qualifier (16th Event)
0x66 Event Code low byte (16th Event) Event Code high byte (16th Event)
Module status (status word)
0x67 - FCE - - - COM V1 - V2 - - - - - - DIAG