Commissioning
Connecting the device to a Siemens PLC in PROFINET
46
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
8.7.4 Setting the IP address in TIA Portal
Select Device view Ò Properties Ò Ethernet addresses.
Assign the desired IP address.
Fig.41: Assigning the IP address
8.7.5 Configuring device functions
The TBEN-S2-4IOL appears as a modular slave with twelve empty virtual slots. Slots 0 and Basic
are pre-configured.
The function of the twelve empty slots is already defined in the GSDML file. The slots can only
be used for a specific purpose.
Slot Meaning
0 Main module turck-tben-s2-4iol (default name)
Parameterization of functions (protocol deactivation, etc.), which concern
the complete module.
XI Parameterization of PROFINET functions (MRP, etc.)
X1 P1 Parameterization of the Ethernet port properties (topology, connection op-
tions, etc.).
X1 P2
Basic Parameters/diagnostics for the DXP-channels of the device (DXP 1, 3, 5 and
7) and Data Valid Signal from the IO-Link ports.
IO-Link port 1…4 Configuration of the 4 IO-Link ports
Diagnostics Optional mapping of the diagnostics (IO-Link and DXP-diagnostics) into the
master's process image.
IO-Link Events Optional mapping of the IO-Link events into the master's process image.
Module status Optional mapping of the module status into the masters process image.