EasyManua.ls Logo

turck TBEN-S2-4IOL - Data Width

turck TBEN-S2-4IOL
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
Commissioning the device in Modbus TCP
60
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Register 0x113E and 0x113F: Save Modbus-Connection-Parameters
Registers 0x113E and 0x113F are used for the non-volatile saving of parameters in registers
0x1120 and 0x1130 to 0x113B.
Procedure:
Write 0x7361 to register 0×113E.
Write 0x7665 ("save") within 30 seconds in register 0x113F to activate the reset of the re-
gisters. Both registers can also be written with one single request using the function
codes FC16 and FC23.
a The parameters are saved.
8.8.3 Data width
Module Process input Process output Alignment
TBEN-S2-4IOL 208 byte 130 word by word

Table of Contents

Related product manuals