EasyManua.ls Logo

turck TBEN-S2-4IOL - Software Diagnostic Messages

turck TBEN-S2-4IOL
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating
Software diagnostic messages
120
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
LEDDXP 1, 3, 5, 7 Meaning (input) Meaning (output)
Off Input not active Output not active
Green Input active Output active (max. 2 A)
Red Output active with overload/short
circuit
ERR DXP 7 Meaning
White flashing Wink command active
10.4 Software diagnostic messages
The device provides the following software diagnostic messages:
n DSP diagnostics
Diagnostic messages of the universal digital channels of the module (DXP 1, 3, 5, 7).
n IO-Link master diagnostics
The IO-Link master reports problems within the IO-Link communication.
n IO-Link device diagnostics
The device diagnostics map the IO-Link Event Codes (according to the IO-Link specification)
sent from the IO-Link devices to the diagnostic telegram of the master.
Event Codes can be read from the connected devices by using appropriate device tools (e.g.
IODD-Interpreter).
Further information concerning the IO-Link Event Codes and their meaning can be found in
the IO-Link specification or in the documentation of the connected devices.
10.4.1 Status- and control word
Status word
EtherNet/IP™
Modbus
PROFINET Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte 0 Byte 1 V2 - - - - - ARGEE DIAG
Byte 1 Byte 0 - FCE - - - COM V1 -
Bit Description
COM Internal error
The device-internal communication is disturbed.
DIAG Diagnostic messages at the device
FCE The DTM Force Mode is activated, which means, the actual output values may no
match the ones defined and sent by the field bus.
V1 V1 or V2 too low (< 18 V DC).
V2
The status word is mapped into the module's process data.
In EtherNet/IP™ the mapping can be deactivated via the Gateway Class (VSC 100).
NOTE
Activating or deactivating the status and control word modifies the process data
mapping.
Control word
The control word has no function.

Table of Contents