Commissioning
Connecting the device to a Siemens PLC in PROFINET
42
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
8.7 Connecting the device to a Siemens PLC in PROFINET
The following example describes the connection of the devices to a Siemens PLC in PROFINET
by means of the programming software SIMATIC STEP7 Professional V15 (TIA-Portal).
Used hardware
The following hardware components are used in this example:
n Siemens PLC S7-1500
n IO-Link master TBEN-S2-4IOL with the following configuration:
– Port 1: Turck temperature sensor, TS-530-LI2UPN8X-..., IO-Link V1.0
– Port 2: Channel used as DI
– Port 3: Turck linear position sensor, Li100P0-Q25LM0-..., IO-Link V1.0
– Port 4: Turck IO-Link hub: TBIL-M1-16DXP, IO-Link V1.1
Used software
The following software tools are used in this example:
n SIMATIC STEP7 Professional V15 (TIA-Portal)
n GSDML file for TBEN-S2-4IOL (can be downloaded for free as ZIP archive “TBEN-
S_PROFINET.zip” under www.turck.com)
Prerequisites
n The programming software has been started.
n A new project has been created.
n The PLC has been added to the project.