15 Technical Data
Technical Data
Power supply
Supply voltage 24 VDC
Permissible range 18…30 VDC
n IO-Link n 20.4…28.8 VDC
Total current max. 4 A per voltage group
Operating current V1: min. 50 mA, max. 110 mA
V2: min.10 mA, max. 115 mA
Sensor/actuator supply VAUX2 Supply from V2, not short-circuit proof,
max. 4 A per group C0…C3
Potential isolation Galvanic isolation from V1 and V2 voltage group,
voltages up to 500 VDC
Connectors
Ethernet 2 × M8, 4-pole
Power supply 2 × M8, 4-pole
Digital in- /outputs M12, 5-pole
Isolation voltages
V1 to V2 ≥ 500 V AC
V1/V2 to the fieldbus ≥ 500 V AC
System data
Transmission rate 10 Mbps/100 Mbps
Protocol detection Automatic, 192.168.1.254
Web server integrated
Service interface Ethernet via P1 or P2
Field Logic Controller (FLC)
Supported from firmware version 3.1.10.0
Released as of ARGEE version 2.0.25.0
Modbus TCP
Address assignment Static IP, DHCP
Supported Function Codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23
Number of TCP connections 8
Register start address 0 (0x0000)
Register start address 2048 (0x0800)
Local port Port 502, fix setting
EtherNet/IP™
Address assignment according to EtherNet/IP™ standard
Device Level Ring (DLR) Supported
Quick Connect (QC) < 150 ms
Number of Class 3 (TCP) connections 3
Number of Class 1 (CIP) connections 10
Input Assembly Instances 103, 120, 121, 122, 123,124, 125
Output Assembly Instances 104, 150, 151, 152