Technical data
132
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Technical Data
Configuration Assembly Instance 106
PROFINET
PROFINET specification V 2.35
Conformance Class B (RT)
Address assignment DCP
MinCycle Time 1 ms
Fast Start-Up (FSU) < 150 ms
Diagnostics according to PROFINET Alarm Handling
Topology detection Supported
Automatic address assignment Supported
Media Redundancy Protocol (MRP) Supported
System redundancy S2
Network load class 3
Digital inputs
Number of channels 4 DXP and 4 SIO
Input type PNP
Type of input diagnostics Channel diagnosis
Switching threshold EN 61131-2 type 3, PNP
Signal voltage, low level < 5 V
Signal voltage, high level > 11 V
Low level signal current < 1.5 mA
High-level signal current > 2 mA
Input delay 0.05 ms
Potential isolation Galvanic isolation to P1/P2,
voltage proof up to 500 V AC
Digital outputs
Number of channels 4 DXP
Output type PNP
Type of output diagnostics Channel diagnostics
Output voltage 24 VDC from potential group
Output current per channel 0.5 A, short-circuit-proof
Potential isolation Galvanic isolation to P1/P2,
voltage proof up to 500 V AC
IO-Link
Number of channels 4
IO-Link Pin 4 operated in IO-Link mode
IO-Link specification Version 1.1
IO-Link port type Class A
Frame type Supports all specified frame types
Supported devices Max. 32 byte input/32 byte output
n Input data n max. 32 Byte per channel
n Output data n max. 32 Byte per channel