V01.00 | 2019/10
17
Protocol Dependent Functions
The device Supported the following Ethernet protocol specific functions:
PROFINET
n FSU - Fast Start-Up (prioritized startup)
n Topology discovery
n Address assignment via LLDP
n MRP (Media Redundancy Protocol)
EtherNet/IP™
n QC – QuickConnect
n Device Level Ring (DLR)
5.4.2 IO-Link channels
The IO-Link master module has four Class A IO-Link channels.
The four IO-Link channels can be parameterized independently of each other and operated
either in IO-Link mode or in SIO mode (DI).
5.4.3 Configurable digital channels – functions
The device is provided with four digital channels, which can be configured as inputs or outputs
according to the application requirements. In all, up to four 3-wire PNP sensors or four PNP DC
actuators with a maximum output current of 0.5 A can be connected per input or output.