Commissioning
Commissioning the device in PROFINET
38
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Name Size Data type Default
setting
INDEX_CAP2 1 byte UINT8 252 (0xFC)
INDEX_CAP3 1 byte UINT8 253 (0xFD)
INDEX_CAP4 1 byte UINT8 254 (0xFE)
INDEX_CAP5 1 byte UINT8 255 (0xFF)
8.6.7 The IO-Link function block IOL_CALL
The IO-Link function block IOL_CALL is specified in the IO-Link specification "IO-Link Integration
Part 1- Technical Specification for PROFIBUS and PROFINET“".
Depending on the PLC manufacturer, the IO-Link CALL function block can differ from the spe-
cification (for example in the representation or the use of variables).
Fig.36: IOL_CALL in accordance with IO-Link specification
IOL_CALL– input variables
Designation
acc. IO-Link
spec.
Data
type
Meaning
REQ BOOL A rising edge triggers the send command.
ID DWORD Address of the IO-Link master module
Step 7 Classic
n Start address of the input data of the IO-Link master module.
TIA Portal
n older Siemens CPUs (e.g. CPU 315):
Start address of the input data of the IO-Link master module.
n recent Siemens CPUs (e.g. CPU 1511):
HW identifier of the device's "Basic" slot
INDEX_CAP INT Function block instance: 247 to 254, 255
RD_WR BOOL 0 = read access
1 = write access
ENTITY_PORT INT Address of the IO-Link port to be accessed
FI_INDEX INT Fix value (65098): defines the access to be an IO-Link CALL
IOL_INDEX INT Number of the IO-Link index which has to be read
IOL_SUBINDEX INT Definition of a possible sub index.