Identity Object (0x01)
The following description of the Ethernet Link Object is taken from the CIP specification, Vol. 2,
Rev. 2.1 by ODVA & ControlNet International Ltd. and adapted to the Turck products.
Class attributes
Attr. no. Attribute
name
Get/Set Type Value
Dec. Hex.
1 0x01 Revision G UINT 1
2 0x02 Max. object
instance
G UINT 1
6 0x06 Max. class at-
tribute
G UINT 7
7 0x07 Max. in-
stance attrib-
ute
G UINT 7
Instance attributes
Attr. no. Attribute
name
Get/Set Type Value
Dec. Hex.
1 0x01 Vendor ID G UINT Contains the manufacturer ID.
Turck = 0x46
2 0x02 Product
type
G UINT Shows the general product type.
Communications Adapter 12
dez
=
0x0C
3 0x03 Product
code
G UINT Identifies a special product in a
device type.
default: 27247
dec
= 6A6F
4 0x04 Revision
n Major
n Minor
G STRUCT OF:
n USINT
n USINT
Revision of the device which is rep-
resented by the Indentity Object.
n 0x01
n 0x06
5 0x05 Device
status
G WORD WORD
6 0x06 Serial
number
G UDINT Contains the identification number
of the product (the last 3 bytes of the
MAC-ID).
7 0x07 Product
name
G STRUCT OF:
USINT
STRING [13]
i.e.: TBEN-S2-4IOL