Commissioning
Commissioning the device in EtherNet/IP™
68
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Configuration Assembly (instance 106)
The modules support Configuration Assembly.
The Configuration Assembly contains:
10 bytes module configuration data (EtherNet/IP™-specific)
+ 72 bytes (parameter data, depending on device)
The meaning of the input data can be found in chapter “Parameterizing and configuring”.
Byte no. Bit no.
Dec. Hex. 7 6 5 4 3 2 1 0
Device Configuration Data
0…8 0x00…
0x08
- - - - - - - -
9 0x09 - - - - - Eth2
port setup
Eth1
port setup
QuickConnect
(not supported)
DXP channels
10 0x0A - - - - - - - DXP1_SRO
11 0x0B - - - - - - - DXP3_SRO
12 0x0C - - - - - - - DXP5_SRO
13 0x0D - - - - - - - DXP7_SRO
14 0x0E - - - - - - - DXP1_EN DO
15 0x0F - - - - - - - DXP3_EN DO
16 0x10 - - - - - - - DXP5_EN DO
17 0x11 - - - - - - - DXP7_EN DO
IO-Link port parameters
IO-Link port 1
18 0x12 - - - - Operation mode
19 0x13 - - - - - - Data Storage Mode
20 0x14 Cycle time
21 0x15 - - - - - - - Revision
22 0x16 - - - - - - - Quick Start-Up
23 0x17 - - - - - - - GSD
24 0x18 - - - - - - - PCDI invalid
25 0x19 - - - - - - - Deactivate
diagnostics
26 0x1A - - - - - - Mapping PDIN
27 0x1B - - - - - - Mapping PDOUT
28
…29
0x1C…
0x1D
Vendor ID
30…33 0x1E…
0x21
Device ID
34…49 0x22…
0x31
IO-Link port 2
50…65 0x32…
0x41
IO-Link port 3
66…81 0x42…
0x51
IO-Link port 4