Commissioning
Commissioning the device in EtherNet/IP™
70
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Instance 103 – Exclusive Owner
The description of the parameters can be found in chapter “Parameterizing and configur-
ing” [}116]
Word no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status word [}120]
0x00 - FCE - - - - V1 - V2 - - - - - - DIAG
Inputs
0x01 - - - - - - - - DXP7 DI6
(SIO)
DXP5 DI4
(SIO)
DXP3 DI2
(SIO)
DXP1 DI0
(SIO)
Process input data valid
0x02 - - - - - - - - - DVS6 - DVS4 - DVS2 - DVS0
IO-Link – process input data
0x03…
0x12
16 words per port
0x13…
0x22
0x23…
0x32
0x33…
0x42
Diagnostics
DXP channels
0x43 - - - - - - - - ERR
DXP 7
- ERR
DXP 5
- ERR
DXP 3
- ERR
DXP 1
-
IO-Link port diagnostics
Port 1
0x44 GEN
ERR
OVL V
HIGH
V
LOW
ULVE LLVU O
TMP
PRM
ERR
EVT1 EVT2 PD
INV
HW
ERR
DS
ERR
CFG
ERR
PPR -
…
Port 4
0x47 GEN
ERR
OVL V
HIGH
V
LOW
ULVE LLVU O
TMP
PRM
ERR
EVT1 EVT2 PD
INV
HW
ERR
DS
ERR
CFG
ERR
PPR -
IO-Link Events
0x48 Port (1st Event) Qualifier (1st Event)
0x49 Event Code low byte (1st Event) Event Code high byte (1st Event)
…
0x66 Port 16th Event) Qualifier (16th Event)
0x67 Event Code low byte (16th Event) Event Code high byte (16th Event)