EasyManua.ls Logo

turck TBEN-S2-4IOL - Page 94

turck TBEN-S2-4IOL
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
Commissioning the device in EtherNet/IP™
94
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Attr. no. Designation Get/Set Type Meaning
Dec. Hex.
16 0x10 Hardware error G USINT 0 = inactive
1 = active
17 0x11 Maintenance events G USINT 0 = inactive
1 = active
18 0x12 Out-of-specification events G USINT 0 = inactive
1 = active
19 0x13 Parameterization error G USINT 0 = inactive
1 = active
20 0x14 Over temperature G USINT 0 = inactive
1 = active
21 0x15 Lower limit value underrun G USINT 0 = inactive
1 = active
22 0x16 Upper limit value exceeded G USINT 0 = inactive
1 = active
23 0x17 Undervoltage G USINT 0 = inactive
1 = active
24 0x18 Overvoltage G USINT 0 = inactive
1 = active
25 0x19 Overload G USINT 0 = inactive
1 = active
26 0x1A Common error G USINT 0 = inactive
1 = active
27 0x1B Port parameterization error G USINT 0 = inactive
1 = active
Process data
28 0x1C Input data word 0 G USINT
G USINT
43 0x2B Input data word 15 G USINT
44 0x2C Output data word 0 G USINT
G USINT
59 0x3B Output data word 15 G USINT

Table of Contents