Your Trustworthy Industrial IoT Partner www.pusr.com
9
2.3.1. I/O specifications
Table 2 I/O specification
2.3.2. I/O wiring
The left picture in Fig.3 shows an example of digital input (DI) dry contact in which the digital input channel is controlled by a switch
that is wired to the COM pin of the DI port. An external DC power(9~36V) is supplied this external circuit via the wiring of DI pin and
the switch. The position of switch and power supply can be interchanged.
The right picture in Fig.3 shows an example of digital input (DI) wet contact in which the digital input channel.
Inputs
Digital inputs
DI channels
2
Input Type
Dry/Wet contact
Wet contact
On: 9 to 36 VDC
Off: 0 to 2 VDC
Dry contact
On: close
Off: open
Range
9-36V DC
Input filter time
Software configurable,10~65535ms
Analog inputs
Quantity
2
Type
Differential input
Resolution
16 bit
Range
4~20mA current
Accuracy
1% FSR
Outputs
Digital outputs
Quantity
2
Type
Form C SSR Relay
AC Contact Current
Rating
10A / 277V AC at resistive load, NO
5A / 250V AC at resistive load, NC
DC Contact Current
Rating
10A / 28V DC at resistive load
Operating time
10 ms max.
Release time
5ms max.
Mechanical Endurance
10000000 operations