EDGE-3
Soundproof MDC O&M
Page 28
WebUI - Fan Speed
The Fan speed page will allow you to set an alarm if there is a Fan Fail.
To enable an alarm, select Fan Speed from the le hand column. Select the ‘on’ buon and enter at least one email address of
those that need to receive a nocaon. See page 19 to set up SMTP sengs (emails).
Fan Speed Curve should not be changed by anyone who does not understand ‘Ramp rates’ which should be set dependant upon
the equipment being used inside of the cabinet.
Ramp rate: Is the rate at which the fans speed up per degree Celsius from the Base speed. They will keep speeding up at
this rate unl they are running at 100% (10V) i.e. they are not capped. They will hit 100% at a temperature dependant on
the ramp rate set. This does not require a restart it will change when selecng save the sengs.
There will be 2 dierent set ramp rates which are listed in the table below and a custom opon to change the ramp rate by
increasing/decreasing the percentage of fan speed per degree.