8
vacon • 99 Options
57 1057
Identification Identification run has failed.
Check that motor is connected
to the drive.
Ensure that there is no load on
the motor shaft.
Ensure that the start command
will not be removed before
completion of identification run.
58 1058
Mechanical brake
Actual status of mechanical brake
remains different from the control sig-
nal for longer than what is defined.
Check the status and connec-
tions of the mechanical brake.
63 1063
Forced Stop fault Forced stop activated
Check reason for forced stop
activation. Once found and cor-
rective actions taken, reset the
fault and restart the drive.
65 1065
PC communica-
tion fault
The data connection between the PC
and frequency converter is broken
66 1066
Thermistor fault
The thermistor input has detected an
increase of motor temperature
Check motor cooling and load.
Check thermistor connection
(If thermistor input is not in use
it has to be short circuited)
68
1301
Maintenance
counter 1 alarm
Maintenance counter has reached the
alarm limit.
Carry out the needed mainte-
nance and reset counter.
1302
Maintenance
counter 2 alarm
Maintenance counter has reached the
alarm limit.
Carry out the needed mainte-
nance and reset counter.
1303
Maintenance
counter 3 alarm
Maintenance counter has reached the
alarm limit.
Carry out the needed mainte-
nance and reset counter.
1304
Maintenance
counter 4 alarm
Maintenance counter has reached the
alarm limit.
Carry out the needed mainte-
nance and reset counter.
69
1310
Fieldbus map-
ping error
Non-existing ID number is used for
mapping values to Fieldbus Process
Data Out.
Check parameters in Fieldbus
Data Mapping menu.
1311
Not possible to convert one or more
values for Fieldbus Process Data Out.
The value being mapped may
be of undefined type. Check
parameters in Fieldbus Data
Mapping menu.
1312
Overflow when mapping and converting
values for Fieldbus Process Data Out
(16-bit).
76 1076
Start prevented
Start command is active and was
blocked in order to prevent uninten-
tional rotation of the motor during the
first power-up.
Reset drive to restore the nor-
mal operation. The need of
restart depends on the parame-
ter settings.
77 1077
>5 connections
Maximum number of 5 simultaneous
active fieldbus or PC tool connections
supported by the application exceeded.
Remove excessive active con-
nections.
100 1100
Soft fill time-out
The Soft fill function in the PID control-
ler has timed out. The wanted process
value was not achieved within time.
Reason might be a pipe burst.
Fault
code
Fault
ID
Fault name Possible cause Remedy
Table 32. Fault codes and descriptions.