Technical data vacon •
Service support: find your nearest Vacon service center at www.vacon.com
7
7.3 VACON
®
100 X - technical data
Mains connection
Input voltage U
in
3AC 208…240V
3AC 380...480V
Input voltage
tolerance
-15%...+10% continuously
Input frequency 50/60 Hz
Protection class I
Input frequency
tolerance
47.5...66 Hz
Connection to mains Once per minute or less
Starting delay <7 s
Supply network
TN- and IT-network (cannot be used with corner
earthed network)
Short-circuit current Max. short-circuit current has to be < 100kA
Motor connection
Output voltage
3AC 0... U
in
Rated output current
I
N
: Ambient temperature max. +40°C. See
Table 24 and Table 25.
Overload output
current
1.5 x I
N
(1 min/10 min);
1.1 x I
N
(1 min/10 min) only for MM6 0072.
See Table 24 and Table 25.
Starting output current
I
S
for 2 s every 20 s. See Table 24 and Table 25.
Output frequency 0…320 Hz (standard)
Frequency resolution 0.01 Hz
Protection class I
Motor characteristics
AC squirrel cage motors
Permanent magnet motors
Cable type Screened motor cable
Cable maximum length
(full EMC compliance)
C2: 15m
Control
characteristics
Switching frequency
Programmable 1.5…16 kHz;
Default: 6 kHz (MM4 and MM5); 4 kHz (MM6)
Automatic switching frequency derating in case of
overheating
Frequency reference
Analogue input
Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point 8…320 Hz
Acceleration time 0.1…3000 sec
Deceleration time 0.1…3000 sec
Braking
Brake chopper standard in all frames
External brake resistor optional
Control
connections
See chapter 5.