Changing control places
Change of control place from Remote to Local (keypad).
1. Anywhere in the menu structure, push the FUNCT button.
2. Using the arrow buttons, select Local/Remote and confirm with the OK button.
3. On the next display, select Local or Remote and again confirm with the OK button.
4. The display will return to the same location as it was when the
FUNCT button was pushed.
However, if the Remote control place was changed to Local (Keypad) you will be prompted for
keypad reference.
Figure 70. Changing control places.
Accessing the control page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the
Arrow up or the Arrow down button to select Control page and confirm with the OK
button.
3. The control page appears
If keypad control place and keypad reference are selected to be used you can set the
Keypad
Reference
after having pressed the OK button. If other control places or reference values are
used the display will show Frequency reference which is not editable.