Page #34 background image
3
vacon • 32 Descriptions of VACON® option boards
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Encoder connection – Single-ended
Figure 15. HTL type encoder connection (open source) using single-ended inputs
NOTE! Grounding is to be connected only at the AC drive to avoid circulating current in the shield.
Isolate shield at the encoder.
It is recommended to use double shielded cable for encoder connection.
Figure 16. HTL type encoder connection (open collector) using single-ended inputs
NOTE! Grounding is to be connected only at the AC drive to avoid circulating current in the shield.
Isolate shield at the encoder.
It is recommended to use double shielded cable for encoder connection.
OPTA5 parameters
See page 27 and 27.
GND
GND
GND
15V/24V from the OPT-A5-
board or from external supply*
OPT-A5
board
.
.
10 +15V/+24V
9GND
1DIC1A+
2DIC1A-
3DIC2B+
4DIC2B-
5DIC3Z+
6DIC3Z-
7ENC1Q
8DIC1
.
.
*If external supply is used remember
to connect the ground of external
supply to terminal #9 of the OPT-A5
and t o the enco de r gr ou nd
**+15V/+24V
Encoder
Tw i ste d pa i rs
with own shield
+
A+
B+
DIC4
7256.emf
GND
A-
B-
15V/24V from t he OPT-A5-
board or from external supply*
OPT-A5
board
.
.
10 +15V/+24V
9GND
1DIC1A+
2DIC1A-
3DIC2B+
4DIC2B-
5DIC3Z+
6DIC3Z-
7ENC1Q
8DIC1
.
.
*If external supply is used remember
to connect the ground of external
supply to terminal #9 of the OPT-A5
andtotheencoderground
**+1 5V /+24 V
Encoder
Tw is te d pa i rs
with own shield
+
+
+
DIC4
7257.emf

Other manuals for Vacon NXP series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NXP series and is the answer not in the manual?

Vacon NXP series Specifications

General IconGeneral
Communication interfacesRS-485, Ethernet
Storage temperature range-40°C to +70°C
DimensionsVaries by model
WeightVaries by model
Product seriesNXP
Voltage range200 V to 690 V
Input voltage range200 V to 690 V
Frequency range0 Hz to 500 Hz
Control methodVector control
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Enclosure classesIP21, IP54
Braking chopperBuilt-in or external
EMC filterBuilt-in or external
Communication protocolsModbus, Profibus, CANopen, Ethernet
Operating temperature range-10°C to +50°C
Humidity range5% to 95% (non-condensing)
Cooling methodAir-cooled or liquid-cooled

Related product manuals