General information vacon • 7
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1
Requirements for an external power back-up:
- output voltage +24DC±10%, max. ripple voltage 100mV RMS
-max. current 1A
- 1A external fuse (no internal short-circuit protection on the control board
NOTE: Analogue outputs and inputs do not work with only +24V supplied to the control unit.
If there is a +24V/EXT+24V output on the board it is short-circuit protected locally. If one of the +24V/
EXT+24V outputs short-circuits, the others remain powered because of the local protection.
1.4.5 Digital input signal conversion
The active signal level depends on which potential the common input CMA (and CMB if available) is
connected to. The alternatives are +24V or Ground (0V). See Figure 4, Figure 5 and Figure 6.
The 24-volt control voltage and the ground for the digital inputs and the common input (CMA) can
be either internal or external.
Some typical input signal conversion examples are shown below. If you use the internal +24V from
the AC drive, the following arrangements are possible:
Figure 4. If CMA is connected to GND with inboard jumper the internal +24V is used and the CMA terminal
ed not be wired
+24V/EXT+ 24V
DI1
DI2
DI3
GND
Jumper setting: = CMA connected to GND
7225.emf

Other manuals for Vacon NXP series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NXP series and is the answer not in the manual?

Vacon NXP series Specifications

General IconGeneral
Communication interfacesRS-485, Ethernet
Storage temperature range-40°C to +70°C
DimensionsVaries by model
WeightVaries by model
Product seriesNXP
Voltage range200 V to 690 V
Input voltage range200 V to 690 V
Frequency range0 Hz to 500 Hz
Control methodVector control
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Enclosure classesIP21, IP54
Braking chopperBuilt-in or external
EMC filterBuilt-in or external
Communication protocolsModbus, Profibus, CANopen, Ethernet
Operating temperature range-10°C to +50°C
Humidity range5% to 95% (non-condensing)
Cooling methodAir-cooled or liquid-cooled

Related product manuals