vacon • 24 Installation
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3.1.2 Cautions
Vacon drives are meant for
fixed installations only
.
Do not perform any measurements when the AC drive is connected to mains.
The touch current of Vacon AC drives exceeds 3.5 mA
AC
. According to standard
EN61800-5-1, a reinforced protective ground connection must be ensured. See
Chapter 3.1.3.
If the drive is used as a part of a machine, the machine manufacturer is responsible
for providing the machine with a supply disconnecting device (EN60204-1).
Only spare parts delivered by Vacon can be used.
At power-up, power brake or fault reset the motor will start immediately if the start
signal is active, unless the pulse control for Start/Stop logic has been selected.
Futhermore, the I/O functionalities (including start inputs) may change if parameters,
applications or software are changed. Disconnect, therefore, the motor if an
unexpected start can cause danger.
The motor starts automatically after automatic fault reset if the autoreset function is
activated. See the Application Manual for more detailed information.
Prior to measurements on the motor or the motor cable, disconnect the motor cable
from the drive.
Do not touch the components on the circuit boards. Static voltage disharge may
damage the components.
Check that the EMC level of the AC drive corresponds to the requirements of the
supply network.
Make sure that the cooling is sufficient. If the AC drive becomes frequently too hot, the
lifetime of the drive will be shorter than usually.
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf

Table of Contents

Other manuals for Vacon NXP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NXP and is the answer not in the manual?

Vacon NXP Specifications

General IconGeneral
BrandVacon
ModelNXP
CategoryMedia Converter
LanguageEnglish

Related product manuals