GENERAL REQUIREMENTS
Cupboard or compartment
ventilation
The boilers are very high efficiency
appliances. As a consequence the
heat loss from the
appliance casing during operation is
very low. For cupboard or
compartment installations it is
therefore not necessary to provide
any high or low level permanent air
vents for cooling purposes.
Air supply
Detailed recommendations for air
supply are given in BS 5440: Part 2.
It is not necessary to have an air vent
in the room or internal space in which
the boiler is installed.
Electrical supply
A 230 V, ~ 50 Hz single phase
electricity supply fused to 3 Amp.
must be provided in accordance with
the latest edition of BS7671 (IEE
Wiring Regulations) and any other
local regulations that may apply.
The method of connection to the
mains electricity supply must provide
a means of completely isolating the
boiler and its ancillary controls.
Isolation is preferably by the use of a
fused three pin plug and unswitched
shuttered socket outlet, both
complying with the requirements of
BS 1363. Alternatively, a 3 Amp.
fused doublepole switch with a 3 mm
contact separation on both poles may
be used.
This appliance must be earthed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant TURBOmax Plus SERIES and is the answer not in the manual?

Vaillant TURBOmax Plus SERIES Specifications

General IconGeneral
CategoryBoiler
ModulationYes
ModelTURBOmax Plus SERIES
Fuel typeNatural gas
MountingWall-mounted
Heating CircuitSingle
Output24kW, 28kW
Warranty2 years (extendable)

Related product manuals