51
GAS SUPPLY ADJUSTMENTS
(COMMISSIONING PART II)
Gas Rate THERMOcompact 615/2 E
Natural gas 2H
Main burner jet mark
2)
7/120
Gas Rate
1)
[m
3
/h]
Delivered gas
for G20
Output [kW]
6.5 8.0 10.0 12.0 14.0 15.0
0.8 1.0 1.3 1.4 1.7 1.7
Gas Rate THERMOcompact 620/2 E
Natural gas 2H
Main burner jet mark
2)
7/120
Gas Rate
1)
[m
3
/h]
Delivered gas
per G20
Output [kW]
7.7 8.0 10.0 12.0 14.0 16.0 18.0 20.0
0.9 1.0 1.2 1.4 1.7 1.9 2.1 2.3
1)
15 °C, 1013 mbar, dry
2)
The nozzles are stamped with the mark shown in
this table. The marking corresponds to the nozzle
hole diameter multiplied by 100.
Table G.4: Gas flow rate
Gas Rate THERMOcompact 624/2 E, TURBOmax Plus 824/2 E
Natural gas 2H
Main burner jet mark
2)
7/120
Gas Rate
1)
[m
3
/h]
Delivered gas
for G20
Output [kW]
10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0
1.2 1.4 1.7 1.9 2.1 2.4 2.6 2.8
Gas Rate THERMOcompact 628/2 E, TURBOmax Plus 828/2 E
Natural gas 2H
Main burner jet mark
2)
7/120
Gas Rate
1)
[m
3
/h]
Delivered gas
per G20
Output [kW]
14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0
1.7 1.9 2.1 2.4 2.6 2.8 3.1 3.3
8.9
1.1
12.0
1.5
10.4
1.3